INTU FR COLLAR
INTU FR WRAP L
March 27, 2017
INTU FR GRILLE
March 16, 2018
Show all
INTU_FR_COLLAR_1_CE_500

INTU FR COLLAR

The firestop collar INTU FR COLLAR is composed of a flexible insert made of graphite-based material that swells under the influence of temperature above 140°C and an external casing made of 1.0 mm steel sheet protected against corrosion by a red paint coating. The steel collar casing is equipped with
a lock used for strapping the ends and stabilizing it on the pipe, as well as mounting brackets fixing the collar to the partition. The collars ensure fire resistance class up to max EI 240.

INTU FR COLLAR TDS EN

Content in accordance with TDS PW_2.5

Where to use

INTU FR COLLAR is used for fire protection of penetrations with plastic pipes (PVC, PP, PE, HDPE) running through fire partitions (flexible walls, rigid walls, floors)

 

Please check above PDF TDS for full:

 

 

 

Compliance

Compilance:

  • Reference standard:
    EN 1366-3 / ETAG 026-2 / EAD 350454-00-1104
  • DoP 2/2019
  • ETA-19/0844
  • CoC 1488-CPR-0825/W
  • TDS
  • SDS
  • Fire classification 03777/18/Z00NZP

 

Availability