INTU FR FOAM 2K
INTU FR MASTIC
21 sierpnia, 2018
INTU FR BANDAGE
17 sierpnia, 2023
Pokaż wszystkie
3-1-0001_WEB

INTU FR FOAM 2K

The INTU FR FOAM 2K intumescent fire protection foam is on the basis polyurethane with fire-retardant additives for the fire-resistant sealing of openings around cable trays, cable bundles, flammable and non-flammable pipes. After application it reacts and increases its volume. During a fire, the two-component foam prevents fire and smoke from spreading through fire-resistant partitions.

  • fire resistance class up to EI 120
  • quick installation and sealing hard-to-reach penetrations
  • installation from one side possible
  • very efficient processing
  • excellent adhesion to surface
  • mixed penetration seal, cable ladders, cable bundles
  • plastic, aluminium composite and metal pipes
  • for use in walls and floors

 

 

INTU FR FOAM 2K TDS EN

Where to use

The INTU FR FOAM 2K intumescent fire protection foam is cartridges on the basis of polyurethane. Is intended to be easy used as mixed penetration seal to the fire resistance performance of flexible wall, rigid wall and rigid floor construction where they have been  provided, with apertures which are penetrated by various cables, waveguides, conduits / tubes, metal pipes, plastic pipes and cable support constructions (perforated or non-perforated steel cable trays and steel ladders).

Rigid walls:

The wall must be 100 mm minimum thickness. Must have concrete, aerated concrete, cellular concrete, reinforced concrete or masonry structure, with min. density ρ ≥ 450 kg/m3.

 

Rigid floors:

The floor must be 150 mm minimum thickness. Must have concrete, aerated concrete, cellular concrete, reinforced concrete or masonry structure, with  min. density ρ ≥ 450 kg/m3.

Flexible walls:

The wall must be minimum thickness 94 mm. Must have steel or timbers profile structure covered on both sides with minimum 2 layers of boards with minimum thickness 12,5 mm or minimum one layer of boards (minimum thickness 25 mm) with classification.

  • For timber stud walls there shall be a minimum distance of 100 mm of the penetration seal to any timber stud. This cavity between the penetration seal and the timber stud has to be closed with insulation.

Compilance

Compilance:

  • ETA-10/0431, OIB
  • ETA-11/0206, OIB
  • EC Certificate of Conformity 0761-CPD-0187
  • EC Certificate of Conformity 0761-CPD-0208
  • DoPZZ330-20180701
  • TDS
  • SDS

Availability

Installation

Transport & storage

Store in dry and cool conditions at temperatures  between + 5°C and + 25°C.

This site uses cookies. More information.

The cookie settings on this website are set to "allow cookies" to give you the best browsing experience possible. If you continue to use this website without changing your cookie settings or you click "Accept" below then you are consenting to this.

Close