The intended use of ablative paint INTU FR UNICOAT P is reinstate the fire resistance performance of flexible wall, rigid wall or rigid floor constructions, where they are penetrated by services: large penetration of cables or single and multiple penetration of non-combustible pipes. The INTU FR UNICOAT P paint should be applied at the recommended length and with the required dry layer thickness.
INTU FR UNICOAT P is an ablative paint used to form penetration seals where metal and combustible pipes and cables, single or in bundles, cable ladders and cable trays, penetrate walls and floors.
Flexible walls: The wall must have a minimum thickness 100 mm, must comprise timber or steel studs lined on both faces with minimum two layers (with overall board layer thickness on one side equal to or greater than 25 mm) of gypsum plasterboards.
Rigid walls: The wall must have a minimum thickness 100 mm, must comprise concrete or masonry separating elements, with a minimum density 450 kg/m3.
Rigid floors: The floor must have a minimum thickness 150 mm, must comprise aerated or reinforced concrete, concrete, with a minimum density 550 kg/m3.
• Test standard: EN 1366-3 / EAD 350454-00-1104
• European Technical Assessment: ETA 24/1047 of 19/12/2024
• Declaration of Performance: DoP 6/2024
• Certificate of Constancy of Performance: 1488-CPR-1149/W
Store in dry and cool conditions at temperatures between +5°C to +35°C.
This site uses cookies. More information.
The cookie settings on this website are set to "allow cookies" to give you the best browsing experience possible. If you continue to use this website without changing your cookie settings or you click "Accept" below then you are consenting to this.