INTU FR GRAPHITE
INTU FR BANDAGE
August 17, 2023
INTU FR DISC
August 17, 2023
Zeige alles
INTU_FR_GRAPHITE_WEB

INTU FR GRAPHITE

The INTU FR GRAPHITE is an insulating and intumescent mass based on graphite, designed for fire resistant sealing of combustible pipes as well as small and medium-sized openings. The types of service penetrations that can be sealed with INTU  FR GRAPHITE are: electrical cables, coaxial cables, fibre-optic cables, bundles of copper pipes for air conditioning. The mass effectively fills the gaps around the service penetration, ensuring that the partition maintains the integrity and insulation with a fire resistance class up to EI120 (details according to the referential documents). Under a high temperature (about 140˚C), the mass swells and closes the opening, preventing the spread of fire.

 

INTU FR GRAPHITE TDS EN

 

Where to use

INTU FR GRAPHITE – an intumescent sealing mass is used for fire protection
of penetrations of plastic pipes, electrical cables, coaxial cables, opt fibre cables that are led in casing pipes or without them. Fire protection of:

 

  • combustible pipes diameter of Ø ≤ 110mm
  • steel pipes diameter Ø ≤ 16mm
  • single cables diameter Ø ≤ 21mm, cable bundles, fibre optics in casing pipes diameter Ø ≤ 37mm
  • cables in AROT type pipes up to Ø110 mm diameter
  • bundles of copper pipes for air conditioning
  • perfect for installation in hard -to-reach places
  • sealing of irregularly shaped penetrations
  • sealing of penetrations without service installations

 

Flexible walls:

The wall must be minimum 100 mm thickness with a frame structure of steel
or wooden sections covered on both sides with a minimum of 2 layers of panels with a thickness of min 12,5 mm.

Rigid walls:

The wall must be minimum 100 mm thickness, made of concrete, reinforced concrete, concrete blocks, cellular concrete, ceramic brick (solid, hollow
or lattice) or silicate brick (solid or hollow) with a density of min. 600 kg/m3.

Rigid floors:

The floor must be at least 150 mm thick made of concrete, reinforced concrete
or cellular concrete with a minimum density of 550 kg/m3.

Compilance

  • Reference standard: EN 1366-3 / EAD 350454-00-1104
  • TDS

Availability

Installation

Transport & storage

Store in dry and cool conditions, at a temperature between +5°C to +25°C. Usefulness 12 months from the date of production placed on the package.

This site uses cookies. More information.

Wichtig: Die Website verwendet Cookies.

Als Teil unserer Website verwenden wir Cookies, um Ihnen Dienstleistungen auf höchstem Niveau anzubieten, auch auf eine Weise, die auf die individuellen Bedürfnisse zugeschnitten ist. Wenn Sie die Website verwenden, ohne die Cookie-Einstellungen zu ändern, werden diese auf Ihrem Endgerät gespeichert. Sie können Ihre Cookie-Einstellungen jederzeit ändern.