INTU FR MASTIC
INTU FR GRILLE DS/DP
August 21, 2018
INTU FR MORTAR
August 21, 2018
Show all
INTU_FR_MASTIC_1_500_ce

INTU FR MASTIC

INTU FR MASTIC is an acrylic mastic designed to prevent spreading of fire, smoke and gases through openings in fire rated walls and floors. INTU FR MASTIC expands when it is subjected to fire and close openings around pipes or cables by creating tight barrier for fire, smoke and gas. Mass effective fills the gaps around the installation, ensuring the integrity and insulation of fire resistance class EI 120 and
EI 240 (details according to compliance documents).

INTU FR MASTIC TDS EN

Content in accordance with TDS PW_2.3

Where to use

INTU FR MASTIC is designed for:

  • fire protection of penetrations with non-flammable pipes in floors or walls
  • fire protection of single electric cables / bundle of cables in floors and walls
  • fire protection of gaps / expansion joints
  • installation / sealing of intumescent ventilation grilles INTU FR GRILLE

Compliance

Compilance:

  • Reference standard: EN 1366-3 / ETAG 026-2 / EAD 350454-00-1104
  • DoP 8/2019
  • ETA 19/0038
  • CoC 1488-CPR-0756/W
  • TDS
  • SDS

 

Availability

Installation

  1. PREPARATION
    1. Do not use INTU FR MASTIC if the ambient temperature is below 5°C.
    2. Clean the surfaces thoroughly from grease and other contaminants before applying the mastic. The INTU FR MASTIC should not be used on substrates that exude oils, softeners or solvents, greases and other contaminants
  2. APPLICATION – fire protection of penetration pipes and cables
    1. Insert a mineral wool primer into the hole with density of 40 kg/m3 to a depth according table 1 for pipes or according fig. 5 and 6 for cables.
    2. Fill the gap with INTU FR MASTIC to the required depth according table 1
      for pipes or according fig. 5 and 6 for cables.
    3. Insulate the pipe from the barrier with mineral wool with a density of min 37 kg/m3 length and thickness indicated in table 1.
  3. APPLICATION – fire protection of gaps / expansion joints
    1. Insert a mineral wool primer into the gaps / expansion joints with density of
      40 kg/m3 to a depth according table 2.
    2. Fill the gap with INTU FR MASTIC to the required depth according table 2.

 