INTU FR COAT A
INTU FR BRICK
March 19, 2018
INTU ATP
March 19, 2018
Show all
INTU_FR_COAT_A_2_500v2

INTU FR COAT A

Firestop ablative paint INTU FR COAT A is a one-component product designed for sealing fire protection penetrations and expansion joints with fire resistance class up to EI 240. Under fire conditions and the influence of high temperature, endothermic reactions take place in the product. The paint absorbs heat to a large extent, delaying the impact of fire on structural elements. The product is used in combination with a mineral wool board with a density of min. 150kg/m3 and a minimum thickness of 60mm for penetration seals and with density of min. 50kg/m3 for linear joint. The ready-made/painted firestop boards INTU FR BOARD A are also available for sale.

Product has BREEAM Attestation.

INTU FR COAT A TDS EN

INTU FR COAT A_BREEAM ATTESTATION

Content in accordance with TDS PK_3.1

Where to use

INTU FR COAT A is designed for:

  • fire protection of penetrations with single non-flammable pipes or groups of non-flammable pipes in floors or walls
  • protection of expansion joints in floors or walls
  • fire protection of electric cables combined with intumescent paint INTU FR COAT I in wall

 

Rigid walls:

The wall must be at least 150mm thick and have concrete, cellular concrete structure or masonry structure, with a minimum density of 600kg/m3

 

Rigid floors:

The floor must be at least 150mm thick and have concrete, cellular concrete structure or masonry structure, with a minimum density of 1700kg/m3

Compliance

Compilance:

  • Reference standard: penetration seals: EN 1366-3 / ETAG 026-2 / EAD 350454-00-1104
    linear joint seals: EN 1366-4 / ETAG 026-3 / EAD 350141-00-1106
  • DoP 5/2019
  • Penetration seals: ETA 19/0038; Linear joint seals: ETA 19/0037
  • Penetration seals: CoC 1488-CPR-0756/W; Linear joint seals: CoC 1488-CPR-0763/W
  • TDS
  • SDS

 

Availability

Installation

  • Prior to sealing, clean the surfaces of the hole and system components from grease and other contaminants thoroughly.
  • Cut the mineral wool board with a density of min 150kg/m3 to the correct size. In the case of linear joint put loose mineral wool density of min. 50kg/m3 or mineral wool board in gap of 100mm depth.
  • Place the wool board in the hole/gap.

 

In the case of non-flammable pipes:

a) mineral wool insulation with a density of min 37kg/m3 should be placed (for exact parameters see Table 1)

b) cover a mineral wool board and a part of the insulation with INTU FR COAT A according to the guidelines in the drawings.

 

In the case of expansion joints, cover the mineral wool board with INTU FR COAT A ablative paint on one side of the partition. Prepare a partition overlap min 5mm.

 

Approximate consumption of INTU FR COAT A for painting a mineral wool boards: 1,7 kg/m– for a dry film thickness of 1 mm.

 

 

 

 

Transport & storage

Store in dry and cool conditions at temperatures between + 5°C and + 25°C.