INTU FR BOARD A

Firestop board INTU FR BOARD A is composed of a mineral wool board with a density of 150kg/m3 and a thickness of 60mm, covered on one side with ablative paint INTU FR COAT A. The product set is designed for sealing fire protection penetrations and preparing fire expansion joints with fire resistance class up to EI 240. In the fire conditions, under the influence of high temperature, endothermic reactions take place in the product. The paint absorbs heat, significantly delaying the impact of fire on structural components.

Product has BREEAM Attestation,

 

INTU FR BOARD A TDS

DECLARATION OF PERFORMANCE

INTU FR BOARD A_ BREEAM ATTESTATION

Content in accordance with TDS PK_2.1

Where to use

INTU FR BOARD A is used for:

  • fire protection of penetrations with single non-flammable pipes or groups of non-flammable pipes in floors or walls
  • protection of expansion joints in floors or walls
  • fire protection of electric cables combined with intumescent paint INTU FR COAT I in wall

 

Rigid walls:

The wall must be at least 150mm thick and have concrete, cellular concrete structure or masonry structure, with a minimum density of 600kg/m3

 

Rigid floors:

The floor must be at least 150mm thick and have concrete, cellular concrete structure or masonry structure, with a minimum density of 1700kg/m3

Compliance

Compilance:

  • Reference standard: penetration seals: EN 1366-3 / ETAG 026-2 / EAD 350454-00-1104, linear joint seals: EN 1366-4 / ETAG 026-3 / EAD 350141-00-1106
  • DoP 5/201Penetration seals: ETA 19/0038; Linear joint seals: ETA 19/0037
  • Penetration seals: CoC 1488-CPR-0756/W; Linear joint seals: CoC 1488-CPR-0763/W
  • TDS
  • SDS

 

Availability

Installation

    1. Prior to sealing, clean the hole surface and system components from grease and other contaminants thoroughly.
    2. Cut the INTU FR BOARD A to the correct size.
    3. Place the INTU FR BOARD A in the hole/gap.
    4. In the case of non-flammable pipes:a) mineral wool insulation with a density of min 37kg/m3 should be placed (for exact parameters see Table 1)
      b) all gaps between system components and the junction of the partition with mineral wool should be filled with INTU FR COAT A.
    1. In the case of expansion joints, cover the mineral wool board with INTU FR COAT A ablative paint on one side of the partition. Prepare a partition overlap min 5mm.

 

 

Transport & storage

Store in dry and cool conditions at temperatures between + 5°C and + 25°C.
Shelf life as specified on the product label.

 